S330M

SCANIA Engine Model – DC09 072A | Fuel – Diesel | Alternator Manufacturer – Mecc Alte | Model – ECO38-2L4A

General Specification
Prime Power (kVA/kW) 300/240
Standby Power (kVA/kW) 330/264
Voltage(V) 400/230
Frequency(Hz) 50

Generator Power is based on power factor of 0.8
Prime Power: Variable load, unlimited hours usage with an average load factor of 80% of the published prime power rating over each 24 hour period.10% overload is available for 1 hour in every 12 hours of operation

Emergency Standby Power: Variable load, limited to 500 hours annual usage up to 300 hours of which maybe continuous running. No overload is permitted

Engine Specification
Manufacturer SCANIA
Model DC09 072A
Fuel Diesel
Cooling System Water
Nominal Operating Speed (rpm) 1500
Displacement (L) 9.3
Number of cylinders and disposition 05, Inline
Aspiration Turbocharged, After cooled
Fuel Consumption at 75% PRP (g/kWh) 41
Fuel Consumption at 100% PRP (g/kWh) 56
Governor Type Electronic
Compression Ratio 16.1
Bore & Stroke (mm) 130 x 140
Electrical System (V) 24
Lubrication Capacity (L) 31
Coolant Capacity (L) 37

Note:

  • The above performance data are valid as per the following specifications
  • Guaranteed within conditions equivalent to those specified in ISO8258-1, ISO3046-1 and B55514-1
  • Diesel fuel is according to B52869 Class A2 or equivalent
  • Lubricant oil is according to M3277 SAE 10W40
  • The coolant should be 50% antifreeze and 50% fresh water
  • Derating may be required for conditions outside these consult Synergy Corporation in case of queries

NB: Information above may be changed without prior notice

More About SCANIA Diesel Generators
Dimensions
Open Type Sound Proof
Length 3000mm 3100mm
Width 1100mm 1100mm
Height 1492mm 1750mm
Weight (Dry) 1850kg
Fuel tank capacity 340
Alternator Specification
Alternator Manufacturer Mecc Alte
Model ECO38-2L4A
Power 300kVA
Insulation class H
Protection grade IP23
Voltage Regulation System Electronic+-0.5%
Pitch Two Third
Number of Bearing 1
Number of Leads 12
Overload long term 100% 1hr in 12
Overload 20 seconds >300%
Number of Phases 3
No. of poles 4
Control System
Controller Make DeepSea 4510/DSE 6010
Engine Protections Oil Pressure
Fuel Level (optional)
Coolant Temperature
Coolant Level (optional)
Generator Protections Over/Under Voltage
Over Current
Over/Under Frequency
Charging Alternator Fault
Inputs and Outputs 3 No’s of Configurable analog Input
4 No’s of binary outputs
4 No’s of binary inputs
D+ Pre Excitation terminal
Event and Performance log Genset Text alarm log
Engine Hours history log
For more features we can use Higher Controller