JD66M

John Deere Engine Model – 4045TF158 | Fuel – Diesel | Alternator Manufacturer – Mecc Alte | Model – ECP32 2M4B

General Specification
Prime Power 60/48
Standby Power (kVA/KW) 66/52.8
Voltage(V) 400/230
Frequency(Hz) 50

Generator Power is based on power factor of 0.8
Prime Power: Variable load, unlimited hours usage with an average load factor of 80% of the published prime power rating over each 24 hour period.10% overload is available for 1 hour in every 12 hours of operation

Emergency Standby Power: Variable load, limited to 500 hours annual usage up to 300 hours of which maybe continuous running. No overload is permitted

Engine Specification
Manufacturer JOHN DEERE
Model 4045TF158
Fuel Diesel
Cooling System Water
Nominal Operating Speed (rpm) 1500
Displacement (L) 4.48
Number of cylinders and disposition 4, Inline
Aspiration Turbocharged, After cooled
Fuel Consumption at 75% PRP (l/h) 12
Fuel Consumption at 100% PRP (l/h) 16
Governor Type Mechanical
Compression Ratio 17:1
Bore & Stroke (mm) 106,127
Electrical System (V) 12
Lubrication Capacity (L) 13.5
Coolant Capacity (L) 23.6

Note:

  • The above performance data are valid as per the following specifications
  • Guaranteed within conditions equivalent to those specified in ISO8258-1, ISO3046-1 and B55514-1
  • Diesel fuel is according to B52869 Class A2 or equivalent
  • Lubricant oil is according to M3277 SAE 10W40
  • The coolant should be 50% antifreeze and 50% fresh water
  • Derating may be required for conditions outside these consult Synergy Corporation in case of queries

NB: Information above may be changed without prior notice

More About JD Diesel Generators
Dimensions
Open Type Sound Proof
Length 1800mm 2600mm
Width 900mm 900mm
Height 1177mm 1800mm
Weight (Dry) 1000kg
Fuel tank capacity 180 L
Alternator Specification
Alternator Manufacturer Mecc Alte
Model ECP32 2M4B
Power 60kVA
Insulation class H
Protection grade IP23
Voltage Regulation System Electronic+-0.5%
Pitch Two Third
Number of Bearing 1
Number of Leads 12
Overload long term 100% 1hr in 12
Overload 20 seconds >300%
Number of Phases 3
No. of poles 4
Control System
Controller Make DeepSea PLC/DSE 4610/6010
Engine Protections Oil Pressure
Fuel Level (optional)
Coolant Temperature
Coolant Level (optional)
Generator Protections Over/Under Voltage
Over Current
Over/Under Frequency
Charging Alternator Fault
Inputs and Outputs 3 No’s of Configurable analog Input
4 No’s of binary outputs
4 No’s of binary inputs
D+ Pre Excitation terminal
Event and Performance log Genset Text alarm log
Engine Hours history log
For more features we can use Higher Controller